Resideo 4208SN Serialized 8 Zone Remote Point Module
- Can be used on controls that support up to 250 zones
- Can be optionally powered from an external DC power supply to reduce the amount of current draw from the polling loop
- Uniquely identified eight EOLR supervised zones (all zones use 10K resistors, supplied)
Overview
The 4208SN Remote Point Module (RPM) is an eight-zone expander that allows the use of available expansion zones on Honeywell VISTA controls that support V-Plex polling loop devices.
Features
- Can be used on controls that support up to 250 zones
- Can be optionally powered from an external DC power supply to reduce the amount of current draw from the polling loop
- Uniquely identified eight EOLR supervised zones (all zones use 10K resistors, supplied)
- Each zone is identified by a unique serial number, which is assigned via on-board DIP switches
- Detects faults on all zones within 400ms of occurence
- Loops A & B can be programmed for fast (10ms) response
- Provides cover tamper protection, which may be enabled or disabled via on board DIP switches
Specifications
| Physical | 6-7/16" W x 4-1/4" H x 1-1/4" D (163mm x 108mm x 32mm) |
| Electrical: | |
| Polling Loop Voltage | 11V nominal; 8.7 - 14VDC range |
| Current | 33.6mA when polling loop provides power to module, 0.6mA when 12VDC input provides power to module. See chart below. |
| 12VDC Input Voltage | 12V nominal; 9.4 - 14VDC range |
| Expander Sensor Loop Response | Slow: 400msec (all loops) Fast: 10msec (option for loops A and B) |
| Expander Sensor Loop Current | 0.52mA (normal) 1.3mA (shorted) |
| Sensor Loop Max. Resistance | Up to 300 ohms of wire resistence + 10K EOLR |
| Agency Listings | UL985 Household Fire UL1023 Household Bulgary UL609 Commercial Burglary UL864 Commercial Fire CSFM FM (Pending) CUL CE (requires #N6361) |
| For UL Listed Commercial Fire Usage | Use N.O. contacts. Style B supervise these loops using Model #EOL 100 fire listed 10K EOLRs (purchased separately). |
| For UL Listed Commercial Burglary Usage | Use N.O. or N.C. contacts. Supervise using EOLRs supplied. |